9171 Installation Guide
Proprietary & Confidential
Canoga Perkins Metro Ethernet Routing Switch
13
of
26
Fig. 2
-
5: Grounding Installation Sketch When A Grounding Bar is in Switch Room
Description:
(1)
P
ower input of switch
(2)
Ground terminal
of switch
(3)
Protective grounding cable
(4)
Grounding bar of switch room
When there is n
o grounding bar in the installation environment of Ethernet switches, if a mud field is nearby
and grounding electrodes are permitted to bury, angle steel or steel
tube
not less than 0.5 m in length may be
used to directly drive into the ground. At this po
int, the yellow
-
green PE cables of Ethernet switches should be
connected to the angle steel (or steel pole) by welding, and the soldered joint should be treated with
preservatives.
Fig. 2
-
6
Grounding the device through a grounding strip
Description:
(1
)
Power input of switch
(2)
Ground terminal
of switch
(3)
Protective grounding cable
(4)
Ground
(5)
Angle steel